    Experimental study on cooling characteristics of a radiant floor cooling system in Beijing

  • Author

    Li, Qingqing ; Chen, Chao ; Lin, Jie ; Wang, Guojian

  • Author_Institution
    Coll. of Archit. & Civil Eng., Beijing Univ. of Technol., Beijing, China
  • fYear
    2011
  • fDate
    15-17 July 2011
  • Firstpage
    2167
  • Lastpage
    2170
  • Abstract
    The cooling characteristics of a radiant floor cooling system with the embedded pipes for an office building in Beijing had been researched mainly by experiments in this paper. The indoor air and floor temperature changed with supply water and outdoor temperature were tested and analyzed. The experimental results show that: 1) temperature of supply water plays a more important role on the characteristics of a radiant floor cooling system than water velocity and shall be controlled above 17 C to prevent condensation on the floor surface, 2) when the radiant floor cooling system is adopted, indoor mean radiant temperature and operative temperature are lower than air temperature respectively. 3)The vertical air temperature difference is about 2.1-4 1°C at the height of 0.1m to 1.1m above the floor and meets the related standard during 95% of 24 hours in a day.
  • Keywords
    condensation; cooling; floors; heat radiation; pipes; Beijing; condensation; cooling characteristics; embedded pipes; floor temperature; indoor air temperature; office building; outdoor temperature; radiant floor cooling system; supply water; vertical air temperature; Cooling; Floors; Heat transfer; Space heating; Temperature; cooling characteristic; experiment; radiant floor cooling system;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Mechanic Automation and Control Engineering (MACE), 2011 Second International Conference on
  • Conference_Location
    Hohhot
  • Print_ISBN
    978-1-4244-9436-1
  • Type

    conf

  • DOI
    10.1109/MACE.2011.5987407
  • Filename
    5987407