• DocumentCode
    2806502
  • Title

    Overvoltages in secondary circuits of air-insulated substation due to disconnector switching

  • Author

    Bajramovic, Z. ; Turkovic, I. ; Mujezinovic, A. ; Carsimamovic, A. ; Muharemovic, A.

  • Author_Institution
    Fac. of Electr. Eng., Univ. of Sarajevo, Sarajevo, Bosnia-Herzegovina
  • fYear
    2012
  • fDate
    Oct. 30 2012-Nov. 2 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Investigations of the electromagnetic interference indicate that disconnecting switching of the off-loaded busbars is one of the most important sources of electromagnetic interference in the secondary circuits of a power station. Disconnector´s contacts in air-insulated substations (AIS) move slowly causing numerous strikes and restrikes between contacts. Every strike causes high-frequency currents (from a few hundred kHz to a few MHz) tending to equalize potentials at the contacts. These travelling current and voltage waves are the most important sources of electromagnetic coupling to the secondary circuits of instrument transformers, on whose ends high-speed and low-power electronic devices are connected. During disconnector switching malfunctioning of auxiliary circuits can occurred. In this paper results of measurements of overvoltages in the secondary circuits in the AIS Grabovica (Hydro Power Plant - HPP Grabovica) and AIS Kakanj are presented. In order to reduce overvoltages in secondary circuits, measures for mitigation of electromagnetic interference are presented.
  • Keywords
    electrical contacts; electromagnetic coupling; electromagnetic interference; overvoltage protection; power electronics; substation insulation; substation protection; voltage measurement; AIS Grabovica; AIS Kakanj; air-insulated substation; auxiliary circuits; disconnector contacts; disconnector switching; disconnector switching malfunctioning; electromagnetic coupling; electromagnetic interference; high-frequency currents; high-speed electronic devices; low- power electronic devices; numerous strikes; off-loaded busbars; overvoltages measurements; potentials equalization; power station secondary circuits; secondary circuits; travelling current; voltage waves; Current transformers; Electromagnetic interference; Instrument transformers; Substations; Surges; Transformer cores; Voltage measurement; Switching; air insulated substation (AIS); disconnecting circuit breaker (DCB); disconnector; electromagnetic interference (EMI); overvoltages; secondary circuits;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology (POWERCON), 2012 IEEE International Conference on
  • Conference_Location
    Auckland
  • Print_ISBN
    978-1-4673-2868-5
  • Type

    conf

  • DOI
    10.1109/PowerCon.2012.6401266
  • Filename
    6401266