A New Restricted Earth Fault Protection
Author
Jian-cheng Tan ; Hua Wei
Author_Institution
AREVA T&D, Calgary
fYear
2007
fDate
22-26 April 2007
Firstpage
276
Lastpage
279
Abstract
A new ground differential or restricted earth fault (REF) protection algorithm is proposed. The paper analyses the sensitivity of the overall phase differential protection on impedance grounded delta-star power transformers, and the need for more sensitive ground fault protection. The paper examines the performance of the widely used Dual Slope Percentage Restraint REF principle, as well as the new REF algorithm, their performance under inrush, and/or external faults conditions in conjunction with CT saturation. Playback tests on both REF elements have indicated the proposed new REF is of superior stability during external fault conditions, and is inherently not affected by inrush conditions.
Keywords
earthing; fault currents; power transformer protection; differential protection; dual slope percentage restraint REF principle; impedance grounded delta-star power transformer; restricted earth fault protection; Circuit faults; Delay effects; Earth; Fault currents; Impedance; Power transformers; Protective relaying; Relays; Saturation magnetization; Surge protection;