DocumentCode :
2811465
Title :
The features of high voltage motor interruption by vacuum circuit breaker with different cable lengths
Author :
Naveed, Syed A. ; Venu Gopala Rao, M. ; Amaranath, J. ; Kamakshaiah, S. ; Singh, B.P.
Author_Institution :
Jawaharlal Nehru Technol. Univ., Hyderabad, India
fYear :
2005
fDate :
16-19 Oct. 2005
Firstpage :
705
Lastpage :
708
Abstract :
This paper describes the high voltage transients are generated in a system, when a 6.6 kV, 400 kW motor is operated through vacuum circuit breaker and can also explain the power failure of the motor. A model has been developed and simulated by using MATLAB. From the result of the simulation, it is observed that the distribution of the voltages provide a greater insight into the surge voltages actually transmitted in the coils. In this study various cable lengths have been considered. For shorter cable length the magnitude of switching transients is higher as compare to the large cable length.
Keywords :
cables (electric); coils; electric machine analysis computing; electric motors; failure analysis; mathematics computing; surges; switching transients; vacuum circuit breakers; voltage distribution; 400 kW; 6.6 kV; MATLAB simulation; cable length; coil; high voltage motor interruption; high voltage transient; power failure; surge voltage; switching transient; vacuum circuit breaker; voltage distribution; Circuit breakers; Circuit simulation; MATLAB; Mathematical model; Power cables; Power generation; Power system modeling; Surges; Vacuum systems; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2005. CEIDP '05. 2005 Annual Report Conference on
Print_ISBN :
0-7803-9257-4
Type :
conf
DOI :
10.1109/CEIDP.2005.1560780
Filename :
1560780
Link To Document :
بازگشت