Abstract :
Voltage sags can be a huge problem for many industries. Voltage sags lasting for hundred milliseconds can shutdown an industry for several hours, due to long start-up times. This will imply large costs for the company due to the subsequent loss in the production. Metal processes, especially the hot rolling mill, have been studied at the steel mill SSAB Oxelosund in Sweden. Calculations of time constants have been done for the process and these are compared to the duration times of measured voltage sags at the same industry. In the worst case, voltage sag duration time of 10 ms may shutdown the rolling mill process. Suggestions of methods to reduce the problem of the process in connection with voltage sags are presented
Keywords :
hot rolling; industrial power systems; power supply quality; power system faults; power system transients; rolling mills; Sweden; hot rolling mill process; metal processes; power quality; ride-through investigations; shutdown; time constants; voltage sag duration time; voltage sags; Costs; Milling machines; Power quality; Power system stability; Production; Slabs; Steel; Time measurement; Voltage fluctuations; Voltage measurement;