Title :
Operation of dynamic voltage restorers without zero sequence compensation capability
Author :
Starling, Leonardo Müller V ; Oliveira, Filipe Dias ; Silva, Sidelmo M. ; De J Cardoso Filho, Braz
Author_Institution :
Dept. of Electr. Eng., Fed. Univ. of Minas Gerais, Belo Horizonte, Brazil
Abstract :
Dynamic voltage compensators have been playing important role in the protection of sensitive loads against disturbances, as voltage sags and swells. One implementation option for such equipment is based on the use of a conventional three-phase inverter, which is not able to inject zero sequence components. This paper evaluates the performance of a dynamic sag compensator without zero sequence injection capability in the protection of sensitive loads. A full scale prototype (220V/250kVA) was implemented and some experimental results of its operation are included to support the theoretical analysis.
Keywords :
invertors; power supply quality; dynamic sag compensator; dynamic voltage restorers; three-phase inverter; zero sequence compensation capability; Energy storage; Inverters; Mathematical model; Power quality; Switches; Topology; Voltage fluctuations;
Conference_Titel :
Industry Applications (INDUSCON), 2010 9th IEEE/IAS International Conference on
Conference_Location :
Sao Paulo
Print_ISBN :
978-1-4244-8008-1
Electronic_ISBN :
978-1-4244-8009-8
DOI :
10.1109/INDUSCON.2010.5739958