• DocumentCode
    2816983
  • Title

    Wet tests on naturally polluted glass and composite insulators

  • Author

    Taklaja, Paul ; Niitsoo, Jaan ; Palu, Ivo

  • Author_Institution
    Dept. of Electr. Power Eng., TUT, Tallinn, Estonia
  • fYear
    2012
  • fDate
    11-13 June 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The study examines what type of bird excrement contamination will lead to insulator´s flashovers on the Estonian 110 kV overhead power lines. Wet tests made in laboratory with naturally contaminated glass and composite insulators show that traditional (insulator´s surface) contamination will not lead to flashovers and therefore most likely the flashovers are caused by highly conductive bird excrement streamers. The tests also show that using corona rings at composite insulator´s line end fittings, affects the occurring probability of partial discharge extent on wetted insulator.
  • Keywords
    composite insulators; corona; flashover; glass; insulator contamination; power overhead lines; wetting; bird excrement contamination; composite insulator; composite insulator line; conductive bird excrement streamer; corona ring; insulator flashover; naturally polluted glass; overhead power line; partial discharge; voltage 110 kV; wet test; wetted insulator; Birds; Contamination; Flashover; Glass; Insulators; Leakage current; Partial discharges; Glass insulators; bird streamer; composite insulators; naturally polluted insulators; wetting tests;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Quality and Supply Reliability Conference (PQ), 2012
  • Conference_Location
    Tartu
  • Print_ISBN
    978-1-4673-1980-5
  • Electronic_ISBN
    978-1-4673-1978-2
  • Type

    conf

  • DOI
    10.1109/PQ.2012.6256236
  • Filename
    6256236