• DocumentCode
    2817132
  • Title

    New optimized analysis method for measuring extended grounding systems

  • Author

    Lindinger, Martin J. ; Renner, Herwig ; Schmautzer, Ernst

  • Author_Institution
    Graz University of Technology, Institute of Electrical Power Systems, Austria
  • fYear
    2012
  • fDate
    11-13 June 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    The fall-of-potential method is commonly used for grounding measurements. During measurements of extended grounding systems high external influences of the measurement circuit can occur and can lead to measurement errors. Therefore different methods were investigated in the past. In this paper a new one is shown. In fact it is an upgrade of the commonly known beat-frequency method with a combination of a Fourier transform. The new method can avoid the disadvantages of known analysis methods reaching more accurate measurement results — even at environments with high external influences of the measurement circuit. Additional an error estimation of the new method is presented.
  • Keywords
    Current measurement; Fourier transforms; Frequency measurement; Grounding; Harmonic analysis; Measurement uncertainty; Voltage measurement; Fourier transform; Grounding measurements; beat-frequency; electromagnetic interferences (EMI); fall-of-potential method; ground impedance; measurements errors; safety; substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Quality and Supply Reliability Conference (PQ), 2012
  • Conference_Location
    Tartu
  • Print_ISBN
    978-1-4673-1980-5
  • Electronic_ISBN
    978-1-4673-1978-2
  • Type

    conf

  • DOI
    10.1109/PQ.2012.6256244
  • Filename