Abstract :
This article analyzes the influence on hydraulic resistance balance from the temperature differences between supply and return water, the specific frictional resistance of vertical two pipe, thermal pressure and pressure drop of household in the household heating system. It adopts Kirchhoffs law to evaluate the hydraulic balance status of vertical two-pipe down feed direct return system in the household heating system and draws the conclusion that an vertical two-pipe down feed direct return system is more suitable for the household heating system, where there is no balancing regulator. Furthermore, this article calculates the range of the average specific frictional resistance of the common riser, and determines the factors that might affect the hydraulic resistance balance.
Keywords :
pipes; space heating; Kirchhoffs law; household horizontal heating system; hydraulic resistance balance; pressure drop; specific frictional resistance; temperature differences; thermal pressure; vertical two pipe; vertical two-pipe down feed direct return system; Feeds; Heat engines; Resistance heating; Thermal resistance; Water heating; down feed direct return system; household heating; hydraulic resistance balance; specific frictional resistance; thermal pressure;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Mechanic Automation and Control Engineering (MACE), 2011 Second International Conference on
Conference_Location :
Hohhot
Print_ISBN :
978-1-4244-9436-1
Type :
conf
DOI :
10.1109/MACE.2011.5988486
Filename :
5988486
Link To Document :
بازگشت