• DocumentCode
    2823754
  • Title

    Primary high-current testing of relays with low ratio current transformers

  • Author

    Zocholl, S.E. ; Mooney, J.

  • Author_Institution
    Schweitzer Eng. Labs. Inc., Holland, PA, USA
  • fYear
    2004
  • fDate
    1-1 April 2004
  • Firstpage
    182
  • Lastpage
    189
  • Abstract
    This paper serves as one of few references describing primary high-current testing of protective relays using low ratio current transformers. Accurate measurement of high-current magnitudes requires high ratio current transformers. However, it is the practice to apply low ratio CTs based on small motor loads. The protection engineer then relies on the motor relay to trip for the enormous current of a phase-to-phase fault in the motor cable. The assumption is that fault current exceeding 300 times the CT rating can produce a secondary current large enough for a fast instantaneous trip. This leap of faith is based on the lack of knowledge of the highly distorted secondary waveform and how it is processed in the relay. The tests show the limitations of Fourier and cosine filters used in microprocessor relays that extract the fundamental phasors and eliminate harmonics. The tests validate the operation of a cosine-peak adaptive filter designed to cope with the highly distorted saturated waveforms produced by the low ratio CTs subjected to high current. This paper also reports on the results of primary high-current tests of overcurrent, motor, and distance relays using low ratio CTs. Lastly, this paper compares the internal unfiltered event records with MATLAB/spl reg/ simulations of the same cases.
  • Keywords
    adaptive filters; current transformers; overcurrent protection; power engineering computing; power system faults; power system protection; relay protection; relays; MATLAB/spl reg/ simulations; cosine-peak adaptive filter design; distorted secondary waveform; harmonic elimination; high-current magnitude measurement; low ratio current transformers; microprocessor relays; motor cable; phase-to-phase fault; primary high-current testing; protective relays; small motor loads; Adaptive filters; Current measurement; Current transformers; Fault currents; Microprocessors; Power harmonic filters; Protection; Protective relaying; Relays; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2004 57th Annual Conference for
  • Conference_Location
    College Station, TX, USA
  • Print_ISBN
    0-7803-8432-6
  • Type

    conf

  • DOI
    10.1109/CPRE.2004.238491
  • Filename
    1287093