• DocumentCode
    282700
  • Title

    Pressure rise due to a high current internal arc in an MV cubicle model

  • Author

    Pettinga, J.A.J.

  • Author_Institution
    NV Kema, Arnhem, Netherlands
  • fYear
    1989
  • fDate
    8-12 May 1989
  • Firstpage
    32
  • Abstract
    The author discusses pressure-rise tests in SF6 and air on a full-scale model of a 12 and 24 kV three phase MV switchgear with currents from 5 to 20 kA RMS at 10 kV RMS copper electrodes (diameter 30 mm) and an iron plate as a counter electrode and an operating pressure of 0.12 and 0.14 MPa. The tests showed that, even with reduced filling pressure for air, no acceptable correspondence between the test results can be achieved. The rapid increase of pressure that was measured inside the tank, resulting from a short-circuit current, showed that the use of an overpressure relief device almost always leads to an expulsion of hot and decomposed SF6 gas, which is due to the low ratio between working pressure and the setting of the safety pressure relief device
  • Keywords
    arcs (electric); sulphur compounds; switchgear; 0.12 to 0.14 MPa; 10 kV; 12 kV; 24 kV; 5 to 20 kA; SF6; air; high current internal arc; overpressure relief device; reduced filling pressure; short-circuit current; three phase MV switchgear;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 1989. CIRED 1989. 10th International Conference on
  • Conference_Location
    Brighton
  • Print_ISBN
    0-85296-376-9
  • Type

    conf

  • Filename