DocumentCode
282700
Title
Pressure rise due to a high current internal arc in an MV cubicle model
Author
Pettinga, J.A.J.
Author_Institution
NV Kema, Arnhem, Netherlands
fYear
1989
fDate
8-12 May 1989
Firstpage
32
Abstract
The author discusses pressure-rise tests in SF6 and air on a full-scale model of a 12 and 24 kV three phase MV switchgear with currents from 5 to 20 kA RMS at 10 kV RMS copper electrodes (diameter 30 mm) and an iron plate as a counter electrode and an operating pressure of 0.12 and 0.14 MPa. The tests showed that, even with reduced filling pressure for air, no acceptable correspondence between the test results can be achieved. The rapid increase of pressure that was measured inside the tank, resulting from a short-circuit current, showed that the use of an overpressure relief device almost always leads to an expulsion of hot and decomposed SF6 gas, which is due to the low ratio between working pressure and the setting of the safety pressure relief device
Keywords
arcs (electric); sulphur compounds; switchgear; 0.12 to 0.14 MPa; 10 kV; 12 kV; 24 kV; 5 to 20 kA; SF6; air; high current internal arc; overpressure relief device; reduced filling pressure; short-circuit current; three phase MV switchgear;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution, 1989. CIRED 1989. 10th International Conference on
Conference_Location
Brighton
Print_ISBN
0-85296-376-9
Type
conf
Filename
206035