DocumentCode :
282721
Title :
Switching voltages in MV networks: their natures, characteristics and methods to prevent their occurrence or to limit their values
Author :
Schoonenberg, G.C. ; Menheere, W.M.M.
Author_Institution :
Holec NV, Hengelo, Netherlands
fYear :
1989
fDate :
8-12 May 1989
Firstpage :
165
Abstract :
In MV cable networks as applied in the Netherlands, insulation co-ordination is in principle defined by the potential occurrence of switching overvoltages. These overvoltages have different origins. Harm can be caused to the installation by either the amplitude or rising time or both. In this article, the basic phenomena are reviewed, such as normal current chopping, virtual current chopping, multiple restrikes and pre-ignitions. The probability of their occurrence in practice is discussed and possible precautions are mentioned. The authors include a description of a special method to prevent the most severe overvoltages
Keywords :
overvoltage protection; power system protection; switching; MV power networks; Netherlands; current chopping; power system protection; pre-ignitions; restrikes; switching overvoltages;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution, 1989. CIRED 1989. 10th International Conference on
Conference_Location :
Brighton
Print_ISBN :
0-85296-376-9
Type :
conf
Filename :
206061
Link To Document :
بازگشت