• DocumentCode
    28285
  • Title

    Novel Technique for Reducing the High Fault Currents and Enhancing the Security of ADWEA Power System

  • Author

    El Moursi, Mohamed Shawky ; Hegazy, R.

  • Author_Institution
    Electr. Power Eng., Masdar Inst. of Sci. & Technol., Abu Dhabi, United Arab Emirates
  • Volume
    28
  • Issue
    1
  • fYear
    2013
  • fDate
    Feb. 2013
  • Firstpage
    140
  • Lastpage
    148
  • Abstract
    This paper introduces the High Temperature Superconducting Fault Current Limiter (HTS-FCL) as a novel technology for mitigating the high fault currents and enhancing the security of Abu Dhabi Water and Electricity Authority (ADWEA) power system. The transient model of ADWEA power system is developed using the PSCAD/EMTDC simulation program. The transient model is validated in steady state and short circuit analysis with the PSS/E model of ADWEA power system. The proposed model is used to facilitate performing the electromagnetic transient studies for installing the HTS-FCL. The detailed time domain model of the HTS-FCL considering its major components, operation control algorithm, sequence of events and fault detection techniques are developed. The implementation of the HTS-FCLs in the 132-kV network of ADWEA power system is studied. Furthermore, the short-circuit currents levels to utilize all potential system equipments and remove the limitations on the available generation are analyzed. The reduction of the fault currents are evaluated at the buses of suspected high fault currents with installing the HTS-FCL to demonstrate its effectiveness for improving the system performance, reliability and security.
  • Keywords
    fault diagnosis; power system protection; power system reliability; power system transients; short-circuit currents; superconducting fault current limiters; time-domain analysis; ADWEA power system security; Abu Dhabi Water and Electricity Authority power system security; HTS-FCL; PSCAD-EMTDC simulation program; PSS-E model; electromagnetic transient studies; events sequence; fault detection techniques; high fault currents reduction; high temperature superconducting fault current limiter; operation control algorithm; potential system equipments; short circuit analysis; suspected high fault currents; system performance; system reliability; system security; time domain model; transient model; voltage 132 kV; Circuit faults; Fault currents; High temperature superconductors; Impedance; Integrated circuit modeling; Resistance; Security; ADWEA power system; HTS-FCL; fault detection and system security; sequence activation algorithm; transient model;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2012.2207746
  • Filename
    6253282