• DocumentCode
    2833732
  • Title

    Study of voltage sag effects on three-phase transformers

  • Author

    Sainz, L. ; Córcoles, F. ; Pedra, J. ; Guasch, L. ; Herraiz, Sergio

  • Author_Institution
    Dept. of Electr. Eng., UPC, Barcelona, Spain
  • fYear
    2004
  • fDate
    12-15 Sept. 2004
  • Firstpage
    142
  • Lastpage
    147
  • Abstract
    This paper studies the effects of symmetrical and unsymmetrical voltage sags on a three-phase three-legged transformer and a three-phase transformer bank by considering that fault clearing is produced instantaneously in all the phases. The transformer model includes saturation and the parameters have been obtained from experimental measurements. The influence of the sag type, depth, duration and initial point-on-wave on the inrush current peak value is studied. The current peak has periodical dependence on sag duration and the initial point-on-wave, and a linear dependence on depth. Unsymmetrical sags can result in current peaks as high as those of symmetrical sags.
  • Keywords
    fault location; power supply quality; power transformers; fault clearing; initial point-on-wave; inrush current peak value; periodical dependence; symmetrical voltage sag; three-phase three-legged transformer; three-phase transformer bank; unsymmetrical voltage sag; Leg; Load modeling; Null value; Phase transformers; Power quality; Shape; Surges; Tail; Voltage fluctuations; Voltage transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power, 2004. 11th International Conference on
  • Print_ISBN
    0-7803-8746-5
  • Type

    conf

  • DOI
    10.1109/ICHQP.2004.1409343
  • Filename
    1409343