DocumentCode
2833940
Title
The effect of neutral path impedance on voltage and current distortion. Part I. symmetrical and balanced three-phase systems
Author
Emanuel, Alexander E. ; Orr, John A.
Author_Institution
Worcester Polytech. Inst., MA, USA
fYear
2004
fDate
12-15 Sept. 2004
Firstpage
186
Lastpage
190
Abstract
This paper discusses some peculiarities of voltage and current distortion in three-phase four-wire symmetrical and balanced systems, namely the effects of neutral path inductance. It is shown that the neutral path inductance by hindering the flow of zero-sequence harmonic currents through the neutral, also reduces the intensity of these harmonics contained in the line currents. The price to be paid for this beneficial effect is an increase in zero-sequence harmonics contained in the voltage-to-neutral spectrum and an increase in the voltage drop across the neutral path. The line-to-line voltages remain, practically, not affected by the additional voltage drop across the neutral path.
Keywords
electric impedance; harmonic distortion; harmonics suppression; inductance; power supply quality; power system harmonics; balanced three-phase systems; line-to-line voltages; neutral path impedance; neutral path inductance; power quality; symmetrical three-phase systems; three-phase four-wire systems; voltage drop; voltage-current distortions; voltage-to-neutral spectrum; zero-sequence harmonic currents; Circuit optimization; Circuit simulation; Equivalent circuits; Harmonic distortion; Impedance; Inductance; Power engineering and energy; Power harmonic filters; Power quality; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power, 2004. 11th International Conference on
Print_ISBN
0-7803-8746-5
Type
conf
DOI
10.1109/ICHQP.2004.1409351
Filename
1409351
Link To Document