System impacts evaluation of a single-phase traction load on a 115 kV transmission system
Author
Sutherland, P.E. ; Waclawiak, M. ; McGranaghan, M.F.
fYear
2004
fDate
12-15 Sept. 2004
Firstpage
430
Lastpage
435
Abstract
The system impact of a new transit substation may include harmonic distortion, voltage unbalance and flicker. Measurements were taken at a similar substation, and system simulations were performed for the planned substation. It was found that the Metro North train load produced significant levels of third harmonic current. Resonances in the 115 kV system were simulated and found to be at frequencies which are not critical. The decision as to whether to install a harmonic filter is a difficult one. Unbalance and flicker were found to be negligible.
Keywords
power harmonic filters; power system simulation; power transmission; railways; rapid transit systems; resonance; substations; traction; 115 kV; Metro North train load; flicker; harmonic analysis; harmonic current; harmonic distortion; harmonic filter; power system simulation; rail transportation; resonance; single-phase traction load; substation; transmission system; voltage unbalance; Current measurement; Frequency; Power harmonic filters; Power system analysis computing; Power system harmonics; Power system simulation; Rail transportation; Substations; USA Councils; Voltage fluctuations;