DocumentCode :
2838689
Title :
Reversing the power flow in the looped electrical distribution network by using a Cascaded H-bridge D-SSSC
Author :
Saradarzadeh, M. ; Farhangi, S. ; Schanen, J.L. ; Jeannin, P-O ; Frey, D.
Author_Institution :
Sch. of Electr. & Comput. Eng., Univ. of Tehran, Tehran, Iran
fYear :
2011
fDate :
16-17 Feb. 2011
Firstpage :
193
Lastpage :
198
Abstract :
In new configuration of electrical distribution network the distributed generation is connected directly to the medium voltage link. For achieving the total generation of DGs the distribution network radial configuration is changed to the loop or meshed configuration by using a power electronic device in the connection point to control the power flow. Distribution Static Synchronous Series Compensator (D-SSSC) is able to control the power flow between two feeders from different substations. Thanks to use the multilevel converter topology, D-SSSC is connected directly to the line, omitting bulky transformer. Cascaded H-bridge is the best option for this kind of realization. Controlling the power flow in new configuration of electrical distribution system is source of advantages. One of the great impacts of D-SSSC is balancing the power flows of connected feeders, avoiding congestion of feeders and cables damages. This system sometimes needs to reverse the power flow in the line despite of the phase angle between the feeders. The conventional SSSC control strategy uses current phase to inject a voltage in phase with the current to maintain the DC bus voltage at its reference value and a quadratic component to control the power flow. This control strategy is fail to operation while the power reference is reversing due to loosing the current phase track at low and zero line current. In this paper the feasibility of a DSSSC for reversing the power flow is discussed and a new control strategy based on voltage phase track is introduced.
Keywords :
distributed power generation; load flow control; power convertors; power distribution control; static VAr compensators; DC bus voltage; cascaded H-bridge D-SSSC; current phase track; distributed generation; distribution network radial configuration; distribution static synchronous series compensator; loop configuration; looped electrical distribution network; medium voltage link; meshed configuration; multilevel converter topology; power electronic device; power flow control; power flow reversing; power reference; quadratic component; reference value; substations; voltage phase track; Impedance; Load flow; Phase locked loops; Power electronics; Substations; Topology; Voltage control; Cascaded H-bridge; D-SSSC; phase locked loop; power flow control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics, Drive Systems and Technologies Conference (PEDSTC), 2011 2nd
Conference_Location :
Tehran
Print_ISBN :
978-1-61284-422-0
Type :
conf
DOI :
10.1109/PEDSTC.2011.5742415
Filename :
5742415
Link To Document :
بازگشت