Abstract
This paper proposes a complete distributed model for investigating the induced shaft voltage and bearing current in turbo generators due to the interaction with the static excitation systems. This undesirable voltage affects the insulations gradually, lowering the life expectancy of the whole system. If the shaft voltage exceeds the dielectric breakdown voltage level of the lubricating grease film in journal bearings, an electrical discharge current flows through the bearings. In order to inspect the shaft voltage, a passive filter is proposed to overcome the stated issue. Both the proposed model and the passive filtering technique are simulated with SIMULINK, and discussed in detail to confirm the presence of the bearing current and shaft voltage.
Keywords
power filters; turbogenerators; SIMULINK; bearing current; dielectric breakdown voltage level; electrical discharge current; excitation-shaft-bearing model; journal bearings; passive filtering technique; shaft induced voltage; static excitation systems; turbogenerators; Capacitance; Generators; Integrated circuit modeling; Passive filters; Rectifiers; Shafts; Windings; bearing current; breakdown voltage; passive filter; shaft voltage; static excitation system;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics, Drive Systems and Technologies Conference (PEDSTC), 2011 2nd
Conference_Location
Tehran
Print_ISBN
978-1-61284-422-0
Type
conf
DOI
10.1109/PEDSTC.2011.5742447
Filename
5742447
Link To Document