Low-resistance grounding method for medium voltage power systems
         
        
            Author : 
Paul, Dev ; Venugopalan, S.I.
         
        
            Author_Institution : 
ICF Kaiser Eng., Oakland, CA, USA
         
        
        
            fDate : 
Sept. 28 1991-Oct. 4 1991
         
        
        
            Abstract : 
The authors present the basics of ungrounded system and system charging current and review medium-voltage system neutral grounding. Parameters affecting the rating of neutral resistors for low-resistance grounding method are discussed as well as limitations of low-resistance grounding methods. An analysis is made of how system charging capacitance affects the choice of grounding method. It is concluded that a relatively higher magnitude of system charging current would require either low-resistance grounding or high-resistance grounding with trip rather than alarm. At medium voltage either a low-resistance or a high-resistance grounding method can be used, depending on the system configuration, the presence of directly connected motors/generators, and plant process needs.<>
         
        
            Keywords : 
earthing; power systems; low resistance grounding; medium voltage power systems; neutral grounding; Capacitance; Circuit faults; Grounding; Industrial power systems; Medium voltage; Power system planning; Power system protection; Power system transients; Power systems; Surges;
         
        
        
        