  • Abstract
    The study of internal faults in transformers, i.e. the calculation of the fault current and its external detection (phase currents) as a function of the location and the amplitude of the fault, is of great interest. This situation has led the authors to manufacture a special, multiple output transformer. This device, designed on the basis of a 100 kVA MV/LV transformer, has enabled them to carry out numerous turn-to-turn and turn-to-earth short-circuits. In association with these tests, they have developed a digital model of the transformer, validated by the actual measurements. This model, when applied to a HV network transformer, enables the efficiency of the usual protection devices to be examined, in particular that of the transformer differential protection
  • Keywords
    digital simulation; fault currents; monitoring; power engineering computing; power transformers; transformer protection; 100 kVA; HV; digital simulation; fault current; internal faults; model; monitoring; phase currents; power engineering computing; power transformers; short-circuits; transformer differential protection;