DocumentCode :
284438
Title :
A simulation model for transformer internal faults base for the study of protection and monitoring systems
Author :
Bertrand, P. ; Devalland, A. ; Bastard, P.
Author_Institution :
Merlin-Gerlin, Grenoble, France
fYear :
1993
fDate :
17-21 May 1993
Abstract :
The study of internal faults in transformers, i.e. the calculation of the fault current and its external detection (phase currents) as a function of the location and the amplitude of the fault, is of great interest. This situation has led the authors to manufacture a special, multiple output transformer. This device, designed on the basis of a 100 kVA MV/LV transformer, has enabled them to carry out numerous turn-to-turn and turn-to-earth short-circuits. In association with these tests, they have developed a digital model of the transformer, validated by the actual measurements. This model, when applied to a HV network transformer, enables the efficiency of the usual protection devices to be examined, in particular that of the transformer differential protection
Keywords :
digital simulation; fault currents; monitoring; power engineering computing; power transformers; transformer protection; 100 kVA; HV; digital simulation; fault current; internal faults; model; monitoring; phase currents; power engineering computing; power transformers; short-circuits; transformer differential protection;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution, 1993. CIRED. 12th International Conference on
Conference_Location :
Birmingham
Print_ISBN :
0-85296-561-3
Type :
conf
Filename :
225647
Link To Document :
بازگشت