Title :
Effects of multiple stroke lightning impulse currents on ZnO arresters
Author :
Darveniza, M. ; Mercer, D.R. ; Tumma, L.R.
Author_Institution :
Queensland Univ., St. Lucia, Qld., Australia
Abstract :
Multiple stroke lightning ground flashes can impose surges of exceptional severity on the arresters used to protect exposed distribution system equipment. The authors report laboratory studies of the effects of representative multiple impulse currents on zinc-oxide surge arresters of distribution type. The results indicate that sextuple 8/20 μs currents can cause damage to arresters not evident with standard lightning current tests
Keywords :
distribution networks; lightning protection; power system protection; surge protection; zinc compounds; 20 mus; 8 mus; ZnO; distribution system; ground flashes; multiple stroke lightning impulse currents; power system protection; surge protection;
Conference_Titel :
Electricity Distribution, 1993. CIRED. 12th International Conference on
Conference_Location :
Birmingham
Print_ISBN :
0-85296-561-3