    Service experience with numerical relays in distribution systems

  • Author

    Koch, G. ; Michaelis, H.D.

  • Author_Institution
    Siemens AG, Energieversorgung Oberfranken, Germany
  • fYear
    1993
  • fDate
    17-21 May 1993
  • Abstract
    The utility Energieversorgung Oberfranken operates its 20 kV distribution systems in predominantly rural areas with Peterson Coil earthed neutrals and in urban areas with a high percentage of power cables solidly grounded. The individual load areas are fed by some 60, 110/20 kV substations, initially each with only one 40 MVA power transformer, which will not be duplicated until system growth demands it. Therefore, for system availability, in case of loss of one system component, the 110 kV system, as well as the 20 kV distribution system, is meshed. This system configuration requires fast and selective fault clearance, as well as efficient communication facilities for system restoration. Furthermore, for enhancement of system security, comprehensive fault reporting was required for preventive maintenance. It is the utility´s policy to minimize the total costs of the distribution systems i.e. initial equipment costs, as well as operation and maintenance over their entire life time. These considerations lead to a fully numerical relay and control concept
  • Keywords
    distribution networks; earthing; electrical faults; power system protection; relay protection; transformer substations; 110 kV; 20 kV; 40 MVA; 60 kV; Germany; Peterson Coil earthed neutrals; costs; distribution systems; fault clearance; grounding; load; numerical relays; power cables; power system relay protection; power transformer; preventive maintenance; security; substations;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 1993. CIRED. 12th International Conference on
  • Conference_Location
    Birmingham
  • Print_ISBN
    0-85296-561-3
  • Type

    conf

  • Filename
    225676