DocumentCode
2845598
Title
A multiple PWM GTO line-side converter for unity power factor and reduced harmonics
Author
Sukegawa, T. ; Kamiyama, K. ; Takahashi, Junji ; Ikimi, T. ; Matsutake, M.
Author_Institution
Hitachi Ltd., Ibaraki-ken, Japan
fYear
1991
fDate
Sept. 28 1991-Oct. 4 1991
Firstpage
279
Abstract
A multiple PWM GTO line-side converter with low switched frequency has been developed for industrial uses needing both higher capacity and performance. The multiple converter is composed of two GTO converter units parallel connected through an interphase reactor. The switching frequency of the GTO thyristors in the multiple converter can be reduced to a quarter of that in the single converter. It is verified by simulations and experiments with a 2750 kVA GTO converter and inverter system with 500 Hz switching frequency that the system has: (1) a unity power factor, (2) reduced harmonics, (3) bidirectional power flow, and (4) speed regulatory performance equal to that of an advanced cycloconverter drive system.<>
Keywords
power convertors; power factor; pulse width modulation; thyristor applications; 2750 kVA; 500 Hz; bidirectional power flow; interphase reactor; multiple PWM GTO line-side converter; speed regulatory performance; switched frequency; unity power factor; Frequency conversion; Inductors; Power system harmonics; Pulse width modulation; Pulse width modulation converters; Pulse width modulation inverters; Reactive power; Switching converters; Switching frequency; Thyristors;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting, 1991., Conference Record of the 1991 IEEE
Conference_Location
Dearborn, MI, USA
Print_ISBN
0-7803-0453-5
Type
conf
DOI
10.1109/IAS.1991.178167
Filename
178167