Title :
Revision of the criteria for generators specifications and project: the electric parameters and stability-case analysis
Author :
De Arruda Penteado, Aderbal, Jr. ; Reis, Lineu Belico dos ; Alves, Edson Leite ; Uemori, Mauro ; Colombo, Neri
Author_Institution :
Dept. de Energia e Automacao Eletricas, Sao Paulo Univ., Brazil
Abstract :
The authors aim that this article can be an agent of collective reflection for both the hydrogenerator\´s project engineers and the users. It is an invitation to discussions about some, so called, old dogmas, concerning the specification of short circuit ratio (SCR) and subtransient ratio (X"q/X"d), that might deserve a revision under the light of a new technology, now available for the voltage and speed regulators. Transient simulations were performed by the authors in machines projected under the classical way and under new criteria, to allow for comparisons. The results lead to a possible revision of the presently applied practices for those parameters
Keywords :
hydroelectric generators; short-circuit currents; stability; transients; Rosal plant machines; electric parameters; generators specifications; hydrogenerator; short circuit ratio; speed regulators; stability; subtransient ratio; transient simulations; voltage regulators; Circuits; Optical reflection; Power generation economics; Power system reliability; Regulators; Stability analysis; Stability criteria; Synchronous machines; Thyristors; Voltage control;
Conference_Titel :
Electric Machines and Drives, 1999. International Conference IEMD '99
Conference_Location :
Seattle, WA
Print_ISBN :
0-7803-5293-9
DOI :
10.1109/IEMDC.1999.769078