Current monitoring for detecting inter-turn short circuits in induction motors
Author
Stavrou, Andreas ; Sedding, Howard ; Penman, James
Author_Institution
Electr. Authority of Cyprus, Larnaka, Cyprus
fYear
1999
fDate
36281
Firstpage
345
Lastpage
347
Abstract
Analysis of the air gap flux distribution and its dependence on the particular machine configuration is carried out. It is shown that the indicators of the fault presence are the lower sideband of field rotational frequency with respect to the fundamental, together with components that are related to slotting
Keywords
air gaps; electric current measurement; induction motors; magnetic flux; short-circuit currents; MMF disturbance function; air gap flux distribution analysis; current monitoring; doubly slotted machine; fault presence indicators; induction motors; inter-turn short circuits detection; lower field rotational frequency sideband; slotting components; Circuit faults; Degradation; Electric breakdown; Frequency; Induction motors; Insulation; Monitoring; Radiofrequency identification; Stator windings; Voltage;