    Influence of Coordinate Controllable Neutral Reactors on UHV Secondary Arc Current

  • Author

    Wang, Z. Jane ; Yin, Z.D. ; Wang, Michael Mao

  • Author_Institution
    North China Electr. Power Univ., Beijing, China
  • Volume
    2
  • fYear
    2009
  • fDate
    16-18 Oct. 2009
  • Firstpage
    156
  • Lastpage
    159
  • Abstract
    In order to ensure the succeed of auto-reclosing, it is common to adopt shunt reactor and neutral reactors to suppress secondary arc on the head and end of Ultra High Voltage (UHV) transmission lines. However, uncontrollable reactor widely used in practical engineering could not reach the best result of suppressing secondary arc. In this paper, the influence of shunt reactor and neutral reactors under coordinate control is discussed. The quadric-mode transformation is adopted to establish the mathematic model of secondary arc current in the double-circuit transmission line. According to the variation of neutral reactors, the secondary arc current of different fault points is calculated. The results indicate that neutral reactors have a great influence on secondary arc current of different fault point, and the method of coordinate controllable neutral reactors should be taken to suppress secondary arc current.
  • Keywords
    arcs (electric); power transmission lines; UHV secondary arc current; coordinate controllable neutral reactors; double circuit transmission line; mathematic model; quadric-mode transformation; shunt reactor; ultra high voltage transmission lines; Capacitors; Circuit faults; Inductance; Inductors; Mathematical model; Mathematics; Power supplies; Power transmission lines; Shunt (electrical); Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy and Environment Technology, 2009. ICEET '09. International Conference on
  • Conference_Location
    Guilin, Guangxi
  • Print_ISBN
    978-0-7695-3819-8
  • Type

    conf

  • DOI
    10.1109/ICEET.2009.275
  • Filename
    5365497