DocumentCode
2855965
Title
Control and Performance of a Medium-Voltage Transformerless Cascade PWM STATCOM with Star-Configuration
Author
Yoshii, Tsurugi ; Inoue, Shigenori ; Akagi, Hirofumi
Author_Institution
Dept. of Electr. & Electron. Eng., Tokyo Inst. of Technol.
Volume
4
fYear
2006
fDate
8-12 Oct. 2006
Firstpage
1716
Lastpage
1723
Abstract
This paper presents a three-phase transformerless cascade PWM STATCOM intended for installation on industrial and utility power distribution systems. It proposes a control method that devotes itself mainly to meeting a demand of reactive power, as well as to voltage-balancing of the multiple isolated and split dc capacitors. The control method is characterized by fast and stable voltage-balancing performance and easy expansion into a higher number of levels. Experimental waveforms confirm that a 200-V, 10-kVA cascade PWM STATCOM with star-configuration has the capability of inductive to capacitive (or capacitive to inductive) operation at the rated reactive power of 10 kVA within 20 ms, keeping the nine DC mean voltages controlled and balanced, even during the transient state
Keywords
PWM power convertors; static VAr compensators; voltage control; 10 kVA; 200 V; PWM STATCOM; cascade connection; industrial power distribution system; multilevel converters; reactive power; star-configuration; static synchronous compensator; utility power distribution system; Automatic voltage control; Capacitors; Control systems; Medium voltage; Pulse modulation; Pulse transformers; Pulse width modulation; Reactive power control; Space vector pulse width modulation; Voltage control; Cascade connection; STATCOM; Voltage balancing; multi-level converters; reactive power;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 2006. 41st IAS Annual Meeting. Conference Record of the 2006 IEEE
Conference_Location
Tampa, FL
ISSN
0197-2618
Print_ISBN
1-4244-0364-2
Electronic_ISBN
0197-2618
Type
conf
DOI
10.1109/IAS.2006.256767
Filename
4025455
Link To Document