Title :
Ferroresonance in a 13.8 kV Distribution Line
Author :
Sutherland, Peter E. ; Manning, Robert
Author_Institution :
EPRI Solutions Inc., Schenectady, NY
Abstract :
Overvoltages, for which ferroresonance was the suspected cause, were observed in the meter shop of an electric utility company, which was correlated with a broken conductor in a 13.8 kV overhead line. The shape of the distorted waveforms and the presence of many power-factor correction capacitors on the lightly loaded line led to the suspicion that this was the cause. A time-domain electromagnetic transient simulation was used to reproduce the waveforms, verifying that ferroresonance was indeed the cause of the overvoltages
Keywords :
distribution networks; ferroresonant circuits; overvoltage; time-domain analysis; 13.8 kV; distribution line; distribution systems; ferroresonance; overvoltage; power-factor correction; time-domain electromagnetic transient simulation; Capacitance; Capacitors; Conductors; Ferroresonance; Nonlinear distortion; Reactive power; Senior members; Substations; Surges; Transformers; component; distribution systems; ferroresonance; overvoltages;
Conference_Titel :
Industry Applications Conference, 2006. 41st IAS Annual Meeting. Conference Record of the 2006 IEEE
Conference_Location :
Tampa, FL
Print_ISBN :
1-4244-0364-2
Electronic_ISBN :
0197-2618
DOI :
10.1109/IAS.2006.256853