DocumentCode :
2857656
Title :
A study on the relation between alarm deadbands and optimal alarm limits
Author :
Naghoosi, E. ; Izadi, I. ; Tongwen Chen
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Alberta, Edmonton, AB, Canada
fYear :
2011
fDate :
June 29 2011-July 1 2011
Firstpage :
3627
Lastpage :
3632
Abstract :
Using alarm deadbands is a common method for reducing the number of false and missed alarms and amount of chattering. Existing methods for designing alarm deadbands are quite general or need online computations. This paper studies the relation between optimal alarm thresholds and deadbands. Two equations are proposed to estimate the optimal threshold with respect to the deadband and history of the process variable.
Keywords :
alarm systems; condition monitoring; manufacturing processes; alarm deadbands; chattering; industrial process monitoring; optimal alarm limit; optimal alarm threshold; Approximation methods; Equations; Estimation; Fault detection; Indexes; Mathematical model; Optimization;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
American Control Conference (ACC), 2011
Conference_Location :
San Francisco, CA
ISSN :
0743-1619
Print_ISBN :
978-1-4577-0080-4
Type :
conf
DOI :
10.1109/ACC.2011.5991432