    2860398
  • Title

    Simulation and analysis on start criterions of low voltage ride-through control

  • Author

    Zhao, Ke ; Wang, Yanan ; Shen, Hongming ; Huang, Shaofeng

  • Author_Institution
    North China Electric Power University, Beijing, China
  • Volume
    3
  • fYear
    2012
  • fDate
    2-5 June 2012
  • Firstpage
    2317
  • Lastpage
    2322
  • Abstract
    This paper proposes a new start criterion of the crowbar circuits based on doubly fed induction generator (DFIG). The working principle of supply-side and rotor-side converters and control strategy during a fault are investigated briefly. In the case of using the same fault control method, different criterions of starting crowbar have different effects on the performance of LVRT when a three phase fault occurs. Simulation results indicate that the start criterion of detecting feeder voltage in the wind farm makes a good performance of LVRT while choosing the optimum crowbar resistance and the appropriate fault control strategy.
  • Keywords
    Circuit faults; Mathematical model; Reactive power; Rotors; Stators; Voltage control; Wind farms; DFIG; LVRT; crowbar; start criterion;