DocumentCode :
286647
Title :
Harmonic suppression filter for offshore interconnected power system
Author :
Mclean, A. ; McLeay, K. ; Sheldrake, A.
Author_Institution :
BAeSEMA Ltd., UK
fYear :
1993
fDate :
34134
Firstpage :
42522
Lastpage :
42527
Abstract :
In theUK offshore industry there has been an increase, over recent years, in the number of satellite platforms that are fed from mother platforms by submarine power cables of significant length. On such systems electrical resonances caused by the combination of submarine cable capacitance and mother platform power transformer and generator inductance can occur. When combined with harmonic currents produced by power converters on the system, excessive voltage distortion levels can be generated. The authors described the analysis of harmonic distortion on Total Oil Marine´s North Alwyn performance together with the new Dunbar platform. The Dunbar platform is fed by two 22.5 km submarine cables from the North Alwyn platform
Keywords :
electric distortion; electric generators; filters; oil technology; power cables; power system harmonics; power system interconnection; power transformers; submarine cables; 22.5 km; UK; capacitance; electrical resonances; filter; generator; harmonic currents; inductance; offshore industry; oil platforms; power converters; power system interconnection; power transformer; submarine power cables; voltage distortion;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Three Phase LV Industrial Supplies: Harmonic Pollution and Recent Developments in Remedies, IEE Colloquium on
Conference_Location :
London
Type :
conf
Filename :
255847
Link To Document :
بازگشت