• DocumentCode
    2868287
  • Title

    Research on Protective Distance between Arrester and Transformer of 220kV AIS Substation

  • Author

    Zhou, Yuanyuan ; Zhou, Lixing ; Li, Lei ; Gan, Lingxia ; Xu, Yinfeng

  • Author_Institution
    Coll. of Electr. & Inf. Eng., Changsha Univ. of Sci. & Technol., Changsha, China
  • Volume
    2
  • fYear
    2009
  • fDate
    16-18 Oct. 2009
  • Firstpage
    236
  • Lastpage
    239
  • Abstract
    This article according to internal and external actual situation from the typical 220 kV substation connection, ATP-EMTP simulation program is applied to simulate and analyze under all effect is to be considered, the rules of over-voltage from transformer and the position of arrester is founded, and found that if the incoming line of overhead line to open-substation have CVT, the maximum protective distance is 185 meter else 143 m and other incoming line substation set the arrester in front can satisfy impact insulation level, the reference is provided that the distance between arrester and transformer.
  • Keywords
    EMTP; arresters; overvoltage protection; power overhead lines; substation protection; AIS substation; ATP-EMTP simulation program; arrester position; overhead line; protective distance; substation connection; transformer overvoltage; voltage 220 kV; Arresters; Capacitance; Educational institutions; Instrument transformers; Lightning; Power cables; Power engineering and energy; Power transformer insulation; Substation protection; Switches; 220kV substation; arrester; lightning incoming surge; over-voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy and Environment Technology, 2009. ICEET '09. International Conference on
  • Conference_Location
    Guilin, Guangxi
  • Print_ISBN
    978-0-7695-3819-8
  • Type

    conf

  • DOI
    10.1109/ICEET.2009.295
  • Filename
    5366483