Title : 
Research on Protective Distance between Arrester and Transformer of 220kV AIS Substation
         
        
            Author : 
Zhou, Yuanyuan ; Zhou, Lixing ; Li, Lei ; Gan, Lingxia ; Xu, Yinfeng
         
        
            Author_Institution : 
Coll. of Electr. & Inf. Eng., Changsha Univ. of Sci. & Technol., Changsha, China
         
        
        
        
        
        
        
            Abstract : 
This article according to internal and external actual situation from the typical 220 kV substation connection, ATP-EMTP simulation program is applied to simulate and analyze under all effect is to be considered, the rules of over-voltage from transformer and the position of arrester is founded, and found that if the incoming line of overhead line to open-substation have CVT, the maximum protective distance is 185 meter else 143 m and other incoming line substation set the arrester in front can satisfy impact insulation level, the reference is provided that the distance between arrester and transformer.
         
        
            Keywords : 
EMTP; arresters; overvoltage protection; power overhead lines; substation protection; AIS substation; ATP-EMTP simulation program; arrester position; overhead line; protective distance; substation connection; transformer overvoltage; voltage 220 kV; Arresters; Capacitance; Educational institutions; Instrument transformers; Lightning; Power cables; Power engineering and energy; Power transformer insulation; Substation protection; Switches; 220kV substation; arrester; lightning incoming surge; over-voltage;
         
        
        
        