Title :
Effect of the single and three phase switching in the transient stability of an electric power system using the extended equal area criterion
Author :
Ferreira, C. M Machado ; Pinto, J. A Dias ; Barbosa, F. P Maciel
Author_Institution :
Dept. de Engenharia Electrotecnica, Inst. Superior de Engenharia de Coimbra, Portugal
Abstract :
In this paper the transient stability of a test power network is studied and analysed when a phase-to-ground fault occurs on a transmission line. A single and three phase reclosure of the tripped circuit breakers poles in the two ends of the faulted line were simulated. The software package TRANsySTEM that the authors developed for transient security assessment of a multimachine power system was used. These computer programs use the extended equal area criterion. This direct formulation reduces drastically the computing time, since it does not require numerical solution of the differential motion equations of the system. The results obtained with this direct approach were compared with the solutions produced by the Runge-Kutta method
Keywords :
Runge-Kutta methods; differential equations; power system analysis computing; power system security; power system transient stability; power transmission faults; power transmission lines; switching; Runge-Kutta method; TRANsySTEM software package; computer programs; differential motion equations; electric power system; extended equal area criterion; multimachine power system; phase-to-ground fault; single phase reclosure; single phase switching; three phase reclosure; three phase switching; transient security assessment; transient stability; transmission line; tripped circuit breakers poles; Circuit faults; Circuit stability; Circuit testing; Distributed parameter circuits; Power system security; Power system simulation; Power system transients; Power transmission lines; Stability analysis; Transient analysis;
Conference_Titel :
Electrotechnical Conference, 1998. MELECON 98., 9th Mediterranean
Conference_Location :
Tel-Aviv
Print_ISBN :
0-7803-3879-0
DOI :
10.1109/MELCON.1998.699368