    Generation of furanic compounds in transformer oil under accelerated thermal and electrical stress

  • Author

    Verma, P. ; Roy, M. ; Tiwari, R.K. ; Chandra, S.

  • Author_Institution
    Thapar Inst. of Eng. & Technol., Patiala
  • fYear
    2005
  • fDate
    26-26 Oct. 2005
  • Firstpage
    112
  • Lastpage
    116
  • Abstract
    High voltage transformers use Kraft paper to insulate the electrical windings present in the core, which is then subsequently immersed in oil. In service, the temperature of the windings will increase to typically 80degC. If the transformer is loaded to beyond its design ratings, the temperature can exceed 100degC causing the cellulose chains in the paper to cleave at an accelerated rate, resulting in the degradation of mechanical strength and performance of the insulation. If unchecked, this can lead to catastrophic failure of the transformer and accompanying disruption to electricity supply and large economic losses to the operating utility. Furfuraldehyde (FFA) is a chemical by-product, which is released into the oil by the thermal degradation of the paper winding. The concentration of FFA within the oil has been directly related to the condition of the paper insulation. Therefore, efforts are made to find the degradation of paper by evaluating the furfural compounds under accelerated thermal and electrical stress and results are correlated with degree of polymerization and tensile strength of paper. The samples are tested at 120degC, 140degC and 160degC and at electric stress 2.5 kV for 360, 720, 1080 and 1440 hours. It was observed that the Furan analysis was the best method for assessing the condition of paper insulation, as this method required the transformer oil to be sampled out and not the paper from the transformer during on-line operation of the transformer
  • Keywords
    cores; insulation testing; life testing; paper; power transformer insulation; power transformer testing; tensile strength; thermal stresses; transformer oil; transformer windings; 120 C; 140 C; 160 C; 2.5 kV; Kraft paper insulation; accelerated testing; catastrophic failure; cellulose chain; condition assessment; core; degree of polymerization; economic loss; electrical stress; electrical winding; electricity supply disruption; furanic compound generation; furfuraldehyde; high voltage transformer oil; mechanical strength; tensile strength; thermal degradation; thermal stress; Acceleration; Dielectrics and electrical insulation; Oil insulation; Petroleum; Power transformer insulation; Temperature; Tensile stress; Thermal degradation; Thermal stresses; Voltage transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference and Electrical Manufacturing Expo, 2005. Proceedings
  • Conference_Location
    Indianapolis, IN
  • Print_ISBN
    0-7803-9145-4
  • Type

    conf

  • DOI
    10.1109/EEIC.2005.1566270
  • Filename
    1566270