DocumentCode
2882743
Title
Field Experiences with Stationary Lead-Acid Batteries in Photovoltaic Power Plants
Author
Kiehne, H.-A.
Author_Institution
VARTA Batterie AG, Hannover
fYear
1982
fDate
3-6 Oct. 1982
Firstpage
249
Lastpage
252
Abstract
Important for failurefree and economic service is the suitability of the batteries to the special demands of photovoltaic power plants with regard to their capacity, discharge voltage, chargebility, cycle stability, low self discharge rates and little or no maintenance. A special method of power calculation for the estimation of the suitable battery type and capacity based on experience is recommended. Especially in pilot plants there is a need to measure the state of charge of the batteries and to calculate by a microprocessor datas either for power or load management. A special system "logistronic" is desribed. Design descriptions are given on systems installed in containers as well as information on photovoltaic power plants sponsered by the European Cummunities, which have been installed or will be in operation shortly. (Power between 30 and 300 W) Field experiences resulted in a complete system consisting of the following components: ¿ bloc batteries with a special lead selenium alloy, maintenancefree operation 3 years or more, ¿ recombination-catalysts increasing maintenancefree operation up to 15 years, ¿ a control system "logistronic", and ¿ pre-mounted batteries in special containers
Keywords
Batteries; Charge measurement; Containers; Current measurement; Photovoltaic systems; Power generation; Power generation economics; Solar power generation; Stability; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1982. INTELEC 1982. International
Conference_Location
Washington, DC, USA
Type
conf
DOI
10.1109/INTLEC.1982.4793738
Filename
4793738
Link To Document