DocumentCode :
2886740
Title :
Adaptive settings of distance protection to prevent mal-operation under severe voltage fluctuation
Author :
Abidin, Ahmad Farid Bin ; Mohamed, Azah
Author_Institution :
Fac. of Electr. Eng., UiTM, Shah Alam, Malaysia
fYear :
2011
fDate :
27-28 June 2011
Firstpage :
162
Lastpage :
165
Abstract :
A new algorithm for adaptive setting of Zone 3 of distance relays during severe voltage fluctuations is proposed. Conventional relays may mal-operate during under voltage instability condition. The developed algorithm is based on dynamic adjustment of zone 3 setting of distance relays to avoid mal-operation. The proposed algorithm overcomes the pitfall in conventional relays by dynamically changing zone 3 reach setting of the distance relay. The paper describes the new algorithm and presents results obtained from studies on the IEEE 9 bus test system.
Keywords :
fault diagnosis; relay protection; IEEE 9 bus test system; adaptive settings; distance protection; distance relays; mal-operation prevention; voltage fluctuations; voltage instability condition; zone 3 reach setting; Presses; Distance Protection; Dynamic Adjustment; Relay Reach Setting; Voltage Instability;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
System Engineering and Technology (ICSET), 2011 IEEE International Conference on
Conference_Location :
Shah Alam
Print_ISBN :
978-1-4577-1256-2
Type :
conf
DOI :
10.1109/ICSEngT.2011.5993442
Filename :
5993442
Link To Document :
بازگشت