DocumentCode
2890733
Title
Switch Room Cooling - A System Concept with Switch Room Located Cooling Equipment
Author
Ståhl, Lennart
Author_Institution
Ericsson Components AB, Energy Systems Division, Telecom Cooling, S-164 81 STOCKHOLM, SWEDEN
fYear
1994
fDate
11-15 April 1994
Firstpage
335
Lastpage
342
Abstract
To the traditional requirements on cooling systems for switching equipment, are now added, concurrently with rising energy prices and labour costs, requirements on energy- and space-efficiency and installation- and maintenance-friendliness. This paper describes a cooling system based on water, with compact units that can be placed in the same room as the equipment to be cooled by the system. The heat transport from the switching equipment to the system is based on the well-tried principle of natural convection. The central points of this paper are the Switch Room Cooling concept, the principle of natural convection and the energy-saving free-cooling function.
Keywords
Acoustic noise; Automatic control; Control systems; Cooling; Costs; Personnel; Refrigerants; Switches; Telecommunication switching; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Special Conference, 1994. TELESCON '94. The first International
Conference_Location
Berlin, Germany
Type
conf
DOI
10.1109/TELESC.1994.4794355
Filename
4794355