  • Abstract
    This paper recaptures a low frequency oscillation occurred during simulation and finally being resolved in the real grid. Three hypothesis are proposed to tackle this issue, namely the ferro-resonance caused by hasty stepping up, the inrush current derived from remanence in transformer and the parameter resonance between the unit and experiment grid. After being refuted consecutively it is assumed that the auto-excitation system parameter resonates with grid. Expectedly the oscillation vanished by altering the control parameter with proof of some simulation results. At last two conclusions are presented from experimental analysis.
  • Keywords
    ferroresonance; hydroelectric power; power system stability; black-start; ferroresonance; hydropower plant; low frequency oscillation; parameter resonance; Circuit faults; Hydroelectric power generation; Oscillators; Substations; Surges; Transient analysis; black-start; excitation system; low frequency oscillation; parameter resonance; stepping up from zero;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2011 4th International Conference on
  • Conference_Location
    Weihai, Shandong
  • Print_ISBN
    978-1-4577-0364-5
  • Type

    conf

  • DOI
    10.1109/DRPT.2011.5994123
  • Filename
    5994123