DocumentCode
2898444
Title
Pilot project to estimate the centralized volt/VAr control effectiveness
Author
Roytelman, I. ; Wee, B.K. ; Lugtu, R.L. ; Kulas, T.M. ; Brossart, T.
Author_Institution
Siemens Power Syst. Control, MN, USA
fYear
1997
fDate
11-16 May 1997
Firstpage
340
Lastpage
345
Abstract
This paper describes a volt/VAr control (VVC) project in which a centralized network-model based VVC was put in place to control a 13.8 kV distribution subsystem. The goal of the project is to estimate the effectiveness of VVC based on different objective functions, including an objective function for future market economy (revenue maximization). The technical issues which are critical to implementing the VVC are discussed. The effectiveness of VVC for energy conservation and revenue maximization is calculated as an effect due to the immediate (within the span of a few minutes) load to voltage response. This effect is compared with the actual effect calculated based on a fifteen minutes average archived telemetered data
Keywords
centralised control; control system analysis; control system synthesis; distribution networks; economics; energy conservation; power system control; reactive power control; voltage control; 13.8 kV; 15 min; centralized volt/VAr control; control design; control simulation; distribution subsystem; energy conservation; load-to-voltage response; objective functions; pilot project; revenue maximization; Admittance; Centralized control; Costs; Optical wavelength conversion; Reactive power; Reactive power control; Substations; System testing; Topology; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Industry Computer Applications., 1997. 20th International Conference on
Conference_Location
Columbus, OH
Print_ISBN
0-7803-3713-1
Type
conf
DOI
10.1109/PICA.1997.599423
Filename
599423
Link To Document