DocumentCode
2904111
Title
Voltage transformer ferroresonance in cogeneration substation
Author
Vilcheck, William S. ; Haddad, Michael V.
Author_Institution
Westinghouse Electric Corp., Pittsburgh, PA, USA
fYear
1992
fDate
8-12 Jun 1992
Firstpage
148
Lastpage
158
Abstract
An incident in which the series grading capacitance of a 230 kV circuit breaker interacted with the magnetizing reactance of a voltage transformer causing overvoltage and eventual failure of the voltage transformer is described. It is shown that this incident, including the damaging overvoltages, was successfully simulated on a digital computer. Using the same model, proposed solutions derived from transmission experience were evaluated. The most effective solution was applied to the substation circuits and measurements were taken during initial circuit breaker energization and deenergization. Measurement results are compared with analytical results
Keywords
circuit breakers; cogeneration; digital simulation; overvoltage; potential transformers; power system analysis computing; power transformers; substations; thermal power stations; 230 kV; circuit breaker; cogeneration substation; deenergization; digital simulation; energization; failure; ferroresonance; magnetizing reactance; overvoltages; power system analysis computing; power transformers; series grading capacitance; thermal power stations; voltage transformer; Capacitance; Circuit breakers; Circuit simulation; Cogeneration; Computational modeling; Computer simulation; Ferroresonance; Substations; Voltage control; Voltage transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulp and Paper Industry Technical Conference, 1992., Conference Record of 1992 Annual
Conference_Location
Portland, OR
Type
conf
DOI
10.1109/PAPCON.1992.186293
Filename
186293
Link To Document