DocumentCode :
2904714
Title :
New algorithm to detect balanced three phase fault during power swing on transmission lines with communication links
Author :
Qais, Mohammed H. ; Alghuwainem, S.M.
Author_Institution :
Electr. Eng. Dept., King Saud Univ., Riyadh, Saudi Arabia
fYear :
2013
fDate :
2-4 Oct. 2013
Firstpage :
1
Lastpage :
5
Abstract :
Distinguishing a balanced three phase fault from a power swing is difficult since both have similar characteristics. In this paper a new algorithm to detect three phase faults during power swings is proposed. The algorithm is based on separating the power swing blocking (PSB) schemes into two distinct schemes, namely PSB1 and PSB2. The first scheme (PSB1) is dedicated to blocking of zones 2 and 3, whereas the second scheme (PSB2) is dedicated to blocking of zone 1. Every relay send signal to the other relay, then coordination is applied between relays at both ends of protected transmission line using communication link. The proposed algorithm increases the reliability and speed of distance protection to detect three phase faults during power swings.
Keywords :
power system relaying; power transmission protection; relay protection; telecommunication links; PSB schemes; balanced three phase fault detection; communication links; distance protection; power swing blocking; protected transmission line; relay coordination; Impedance; Relays; Reliability; Power swings; distance relays; relay blocking schemes; transmission line protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power and Energy Conversion Systems (EPECS), 2013 3rd International Conference on
Conference_Location :
Istanbul
Print_ISBN :
978-1-4799-0687-1
Type :
conf
DOI :
10.1109/EPECS.2013.6713005
Filename :
6713005
Link To Document :