• DocumentCode
    2905932
  • Title

    Aging of distribution transformers due to harmonics

  • Author

    Singh, R. ; Singh, A.

  • Author_Institution
    Dept. of E.lectr. Eng., Jabalpur Eng. Coll., Jabalpur, India
  • fYear
    2010
  • fDate
    26-29 Sept. 2010
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    Solid state electronics is used to increase the energy efficiency of electrical load devices. The harmonic distortion of current is increasing with the enhanced use of nonlinear loads i.e. solid state devices. Examples of nonlinear loads are personal computer, laptop, laser printer, fax machine, television set (TV), fluorescent tube with electronic ballast, compact fluorescent lamp, battery charger, adjustable speed drives, uninterrupted power supply (UPS) and any other equipment powered by switched-mode power supply (SMPS) unit. These nonlinear loads draw more current than the fundamental current and cause overloading of the components of the distribution system. Transformers are major components of the distribution system and are mainly affected by this overloading. This leads to higher losses, reduces the strength of insulation and consequently leads to reduction of useful life of the transformer. Aging of transformer increases due to overheating caused by overloading. This paper presents the results of a case study of aging of transformer caused by harmonics due to non linear loads. Here two transformers of 500 kVA and 100 kVA are considered which supply a technical institution and residential campus respectively. The harmonic currents produced by these loads are captured in the laboratory and their effect on transformers is studied. An attempt has been made to calculate the energy loss due to harmonic distortion caused by these nonlinear loads. The rise in operating temperature due to harmonic current and hence life expectancy of the transformers are calculated.
  • Keywords
    harmonic distortion; power distribution; power system harmonics; power transformers; switched mode power supplies; SMPS; apparent power 100 kVA; apparent power 500 kVA; distribution transformer aging; harmonic currents; harmonic distortion; overheating; power distribution system; solid state electronics; switched-mode power supply unit; uninterrupted power supply; Computers; Harmonic analysis; Harmonic distortion; Oil insulation; Power system harmonics; Power transformer insulation; Temperature; distribution transformer; energy loss; harmonic distortion; life expectancy; nonlinear load; operating temperature; overloading; temperature rise;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power (ICHQP), 2010 14th International Conference on
  • Conference_Location
    Bergamo
  • Print_ISBN
    978-1-4244-7244-4
  • Electronic_ISBN
    978-1-4244-7245-1
  • Type

    conf

  • DOI
    10.1109/ICHQP.2010.5625347
  • Filename
    5625347