• DocumentCode
    2906638
  • Title

    Direct power control of reduced switch active filters

  • Author

    Baktash, A. ; Jalilian, A. ; Vahedi, A.

  • Author_Institution
    Centre of Excellence for Power Syst. Autom. & Oper., Iran Uni. of Sci. & Technol., Tehran, Iran
  • fYear
    2010
  • fDate
    26-29 Sept. 2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Nonlinear and time variant loads generate harmonic currents in power systems. Active filters (AF) are used to reduce the amplitude of these currents or omit them. Different control strategies have been presented for AF that among them the p-q theory is more popular. In this paper direct power control (DPC) method is used to implement the p-q theory. Active and reactive power of load and AF are measured and command values are calculated to compensate the load reactive power and just the oscillating part of load active power. The used converter is a reduced switch AF and has two switches less than a conventional full bridge AF, so this leads to less cost, complexity and loss. The simulation results show the excellent performance of this structure with zero source reactive power and a dc active power.
  • Keywords
    active filters; power control; power filters; dc active power; direct power control method; nonlinear loads; p-q theory; power systems; reduced switch active filters; time variant loads; zero source reactive power; Converters; Harmonic analysis; Power control; Power harmonic filters; Reactive power; Switches; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power (ICHQP), 2010 14th International Conference on
  • Conference_Location
    Bergamo
  • Print_ISBN
    978-1-4244-7244-4
  • Electronic_ISBN
    978-1-4244-7245-1
  • Type

    conf

  • DOI
    10.1109/ICHQP.2010.5625386
  • Filename
    5625386