DocumentCode
2912264
Title
Stability evaluation of an electromagnetic contactor during voltage sag
Author
Chi, Chieh-Tsung ; Yin, Shih-An
Author_Institution
Dept. of Electr. Eng., Chienkuo Technol. Univ., Changhua
fYear
2008
fDate
17-20 Dec. 2008
Firstpage
571
Lastpage
576
Abstract
The objective of this paper aims at investigating the effects of the power disturbances, in particular, voltage sag upon the dynamic stability of an electromagnetic contactor. By using the basic definitions of passivity conditions or the energy-method, the dynamic stability of contactor can be easily identified by means of detecting the electrical-energy transferring direction during voltage sag. For performing the related qualitative analysis of the contactor, the numerical contactor model is first established based on the magnetic circuit analysis method. Several useful simulation results were conducted and shown that the dynamic stability of ac electromagnetic contactors was apt to be affected by voltage sag events. Finally, the proposed stability evaluation method for the contactor was ensured that it is feasible.
Keywords
contactors; electromagnetic devices; magnetic circuits; power supply quality; stability; dynamic stability; electrical-energy transferring direction; electromagnetic contactor; magnetic circuit analysis method; power disturbances; qualitative analysis; stability evaluation; voltage sag; Circuit analysis; Circuit simulation; Circuit stability; Contacts; Discrete event simulation; Magnetic analysis; Magnetic circuits; Numerical models; Performance analysis; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Control, Automation, Robotics and Vision, 2008. ICARCV 2008. 10th International Conference on
Conference_Location
Hanoi
Print_ISBN
978-1-4244-2286-9
Electronic_ISBN
978-1-4244-2287-6
Type
conf
DOI
10.1109/ICARCV.2008.4795581