DocumentCode
2913336
Title
A novel method to identify the inrush current based on waveform longitudinal symmetry coefficient for transformer protection
Author
Yongli, Li ; Jun, Chen ; Bin, Yao
Author_Institution
Sch. of Electr. Eng. & Autom., Tianjin Univ., China
Volume
C
fYear
2004
fDate
21-24 Nov. 2004
Firstpage
393
Abstract
In this paper, a novel method based on waveform longitudinal symmetry coefficient is proposed to identify the inrush current and fault current for transformer protection. Because the fault current waveform has characteristic of approximate symmetry, its longitudinal symmetry coefficient is nearly zero and less than 0.10. But the inrush current waveform is longitudinal asymmetrical, and its longitudinal symmetry coefficient is larger and more than 0.15 in normal conditions. The result of simulation demonstrated the method is valid and less affected by CT saturation and high harmonics.
Keywords
fault currents; fault location; power transformer protection; fault current identification; inrush current identification; transformer protection; waveform longitudinal symmetry coefficient; Circuit faults; Fault currents; Power system faults; Power system harmonics; Power system protection; Power system simulation; Power system stability; Power transformers; Surge protection; Transmission line discontinuities;