DocumentCode :
2913336
Title :
A novel method to identify the inrush current based on waveform longitudinal symmetry coefficient for transformer protection
Author :
Yongli, Li ; Jun, Chen ; Bin, Yao
Author_Institution :
Sch. of Electr. Eng. & Autom., Tianjin Univ., China
Volume :
C
fYear :
2004
fDate :
21-24 Nov. 2004
Firstpage :
393
Abstract :
In this paper, a novel method based on waveform longitudinal symmetry coefficient is proposed to identify the inrush current and fault current for transformer protection. Because the fault current waveform has characteristic of approximate symmetry, its longitudinal symmetry coefficient is nearly zero and less than 0.10. But the inrush current waveform is longitudinal asymmetrical, and its longitudinal symmetry coefficient is larger and more than 0.15 in normal conditions. The result of simulation demonstrated the method is valid and less affected by CT saturation and high harmonics.
Keywords :
fault currents; fault location; power transformer protection; fault current identification; inrush current identification; transformer protection; waveform longitudinal symmetry coefficient; Circuit faults; Fault currents; Power system faults; Power system harmonics; Power system protection; Power system simulation; Power system stability; Power transformers; Surge protection; Transmission line discontinuities;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
TENCON 2004. 2004 IEEE Region 10 Conference
Print_ISBN :
0-7803-8560-8
Type :
conf
DOI :
10.1109/TENCON.2004.1414790
Filename :
1414790
Link To Document :
بازگشت