• DocumentCode
    2913588
  • Title

    Measurement of transformer oil dielectric strength

  • Author

    Mohsin, M.M. ; Rehrnan, M. ; Nema, R.S. ; Narayanachar, M.N.

  • Author_Institution
    Sch. of Electr. & Electron., Science Univ., Malaysia
  • Volume
    C
  • fYear
    2004
  • fDate
    21-24 Nov. 2004
  • Firstpage
    436
  • Abstract
    This paper deals with the breakdown studies of transformer oil under ac voltage. The oil was filtered, degassed, and then allowed to get saturate with dry air. The breakdown studies were carried out on processed oil at room temperature using brass made spheres of 12.5 mm diameter and Rogowski electrodes of 30.0 mm overall diameter. The vast breakdown voltage data generated by conducting large number of experiments have been found to be normally distributed. Furthermore, it has been observed that for a given value of breakdown probability, the voltage is always higher in case of spheres than Rogowski electrodes for a given oil gap. The breakdown characteristics are also drawn in terms of oil gap for two different electrode systems which may be used as a ready reference for the purpose of designing.
  • Keywords
    dielectric measurement; electric breakdown; electric strength; power transformer insulation; transformer oil; 12.5 mm; 30 mm; Rogowski electrodes; breakdown; dielectric strength measurement; spheres; transformer oil; Breakdown voltage; Circuit faults; Dielectric breakdown; Dielectric measurements; Electrodes; Hydrocarbons; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    TENCON 2004. 2004 IEEE Region 10 Conference
  • Print_ISBN
    0-7803-8560-8
  • Type

    conf

  • DOI
    10.1109/TENCON.2004.1414801
  • Filename
    1414801