• DocumentCode
    2915018
  • Title

    Change of dielectric strength of vacuum interrupters in process of life-time degradation

  • Author

    Alferov, D.F. ; Pertsev, A.A. ; Ryl´skaya, L.A. ; Sidorov, V.A.

  • Author_Institution
    All-Russian Electrotech. Inst. (FGUP VEI), Moscow, Russia
  • fYear
    2010
  • fDate
    Aug. 30 2010-Sept. 3 2010
  • Firstpage
    19
  • Lastpage
    22
  • Abstract
    60 kV vacuum interrupters (VI) for 110 kV circuit-breakers are investigated. Reduction of dielectric strength of VI in process of expiration of an electric resource is revealed at lightning pulse test. It occurs owing to reduction of dielectric strength of system “case-shield” owing to metallization of a part of an internal insulation surface of VI case with products of contact erosion. Metallization increases with reduction of switching resource. Dielectric strength of an inter-contact gap with its sufficient length does not provide dielectric strength of VI. The original shielding system providing preservation of dielectric strength of VI up to expiration of an electric resource is developed and offered.
  • Keywords
    electric strength; metallisation; vacuum interrupters; contact erosion; intercontact gap; internal insulation surface; lifetime degradation; lightning pulse test; metallization; vacuum interrupters dielectric strength; voltage 60 kV; Dielectric breakdown; Insulation; Interrupters; Lightning; Metallization; Switches;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
  • Conference_Location
    Braunschweig
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4244-8367-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2010.5625886
  • Filename
    5625886