DocumentCode
2915018
Title
Change of dielectric strength of vacuum interrupters in process of life-time degradation
Author
Alferov, D.F. ; Pertsev, A.A. ; Ryl´skaya, L.A. ; Sidorov, V.A.
Author_Institution
All-Russian Electrotech. Inst. (FGUP VEI), Moscow, Russia
fYear
2010
fDate
Aug. 30 2010-Sept. 3 2010
Firstpage
19
Lastpage
22
Abstract
60 kV vacuum interrupters (VI) for 110 kV circuit-breakers are investigated. Reduction of dielectric strength of VI in process of expiration of an electric resource is revealed at lightning pulse test. It occurs owing to reduction of dielectric strength of system “case-shield” owing to metallization of a part of an internal insulation surface of VI case with products of contact erosion. Metallization increases with reduction of switching resource. Dielectric strength of an inter-contact gap with its sufficient length does not provide dielectric strength of VI. The original shielding system providing preservation of dielectric strength of VI up to expiration of an electric resource is developed and offered.
Keywords
electric strength; metallisation; vacuum interrupters; contact erosion; intercontact gap; internal insulation surface; lifetime degradation; lightning pulse test; metallization; vacuum interrupters dielectric strength; voltage 60 kV; Dielectric breakdown; Insulation; Interrupters; Lightning; Metallization; Switches;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
Conference_Location
Braunschweig
ISSN
1093-2941
Print_ISBN
978-1-4244-8367-9
Electronic_ISBN
1093-2941
Type
conf
DOI
10.1109/DEIV.2010.5625886
Filename
5625886
Link To Document