  • Abstract
    This paper presents the development of a CPLD-based islanding detection for mini grid connected inverter in renewable energy with very simple under/over voltage and under/over frequency islanding detection algorithms. The system was implemented on a single XC9572 complex programmable logic device (CPLD) chip using schematic based and VHDL based synthesis model The CPLD monitor the under/over voltage and under/over frequency of utility grid and processed the value of voltage and frequency for turned on-off relay between mini grid connected inverter and utility grid.
  • Keywords
    frequency measurement; invertors; programmable logic devices; relays; renewable energy sources; voltage measurement; CPLD; XC9572 complex programmable logic device; inverter; islanding detection algorithm; on-off relay; renewable energy; under-over frequency monitoring; under-over voltage monitoring; Bridge circuits; Costs; Frequency; Inverters; Photovoltaic systems; Power electronics; Protection; Renewable energy resources; Solar power generation; Voltage control;