Experimental Study and System Optimization on Ground Source Heat Pump System in the Heating Mode
Author
Xiaoli, Dai ; Xiaoyan, Wu
Author_Institution
Sch. of Energy & Power Eng., Jiangsu Univ., Zhenjiang, China
fYear
2011
fDate
19-20 Feb. 2011
Firstpage
758
Lastpage
760
Abstract
The paper measures a ground source heat pump system which is running in the heating mode in a hotel in Hunan. And analyze how the circulation loop water flow influences the coefficient of performance of the heat pump units and the whole system. According to operating states of the ground source heat pump system, frequency conversion technology is purposed to be applied in the deep well pump so as to save much energy. The feasibility of the project is demonstrated in detail based on equivalent peak hour theory from energy saving property and static recycling period.
Keywords
energy conservation; ground source heat pumps; optimisation; recycling; space heating; circulation loop water flow; energy saving; frequency conversion technology; ground source heat pump system; heating mode; static recycling; system optimization; energy saving; frequency conversion; ground source heat pump; the coefficient of performance;