DocumentCode :
2926618
Title :
Design of the insulating supports in medium voltage dry-type transformers
Author :
Gonzalez V, E. ; Gómez, P. ; Espino-Cortés, F.P.
Author_Institution :
SEPI - ESIME, Zacatenco Nat. Polytech. Inst., Mexico City, Mexico
fYear :
2011
fDate :
5-8 June 2011
Firstpage :
45
Lastpage :
48
Abstract :
In this work, a study of the parameters that affect the breakdown voltage in dry-type transformer is performed. The effect of the high operation temperatures of the transformer on the voltage breakdown in the insulating supports is investigated and the electric field distribution on different profiles of these supports is modeled using Finite Element Method (FEM). A design of the insulating support that can help to reduce its length without increasing the possibility of breakdown is discussed.
Keywords :
electric fields; finite element analysis; power transformer insulation; FEM; electric field distribution; finite element method; high operation temperatures; insulating supports; medium voltage dry-type transformers; voltage breakdown; Electric breakdown; Electric fields; Finite element methods; Ocean temperature; Oil insulation; Power transformer insulation; Windings; FEM; breakdown; dry-type transformer; electric field; supports;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference (EIC), 2011
Conference_Location :
Annapolis, MD
ISSN :
pending
Print_ISBN :
978-1-4577-0278-5
Electronic_ISBN :
pending
Type :
conf
DOI :
10.1109/EIC.2011.5996113
Filename :
5996113
Link To Document :